Chapter 12

Configuring Hardware for the MicroVAX

Information Processors

12-6

Table 12.B

Test Numbers and Device Mnemonics

This test

number:

Represents this device:

And this

mnemonic:

F

not used

--

E

time of year clock

CLK

D

nonĆvolatile RAM

NVR

C

DZ controller (serial line controller)

DZ

B

memory

MEM

A

memory management unit

MM

9

floating point unit

FP

8

interval timer

IT

7

disk controller (and disk drives)

HDC,

1

SCSIĆA

2

6

tape controller (and program loader)

TPC,

1

SCSIĆB

2

5

interrupt controller and Ethernet ID ROM

SYS

4

not used

--

3

not used

--

2

dual port RAM

BPI

1

Ethernet

NI

1

MicroVax Information Processor (cat. no. 5730ĆCPU1) only

2

MicroVax Information Processor EP or EE (cat. no. 5731ĆCPU1, ĆCPU2) only

If an error summary is displayed, you should look at the system
configuration table. This table displays error codes that help you
determine whether or not to replace the module or a device. The table also
displays the MicroVAX Information Processor’s Ethernet address. For
more information, see page

12-7

.

Run Self-test on Individual Devices
To test individual devices, follow this procedure:

1. Make sure you are at the console prompt:

>>>

2. Enter the

TEST

command and the number of the device you want to

test. For example, to self-test the floating point unit (FP), you would
enter:

TEST 9

You can also run self-tests on a range of devices by entering the first
and last number of the range. For example, to test devices C through
7, you would enter:

TEST C 7

To test all devices, enter:

TEST F 1