Automatic oi, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 158

Advertising
background image

EAGLE QUANTUM PREMIER DEVICES

12-43

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Automatic Oi

The UV X2200 includes the Automatic Optical Integrity (Oi) feature — a calibrated performance test that is

automatically performed once per minute to verify complete detector operation capabilities. No testing with an

external test lamp is required. The detector automatically performs the same test that a maintenance person

with a test lamp would perform —once every minute, 60 times per hour. However, a successful automatic Oi test

does not produce an alarm condition.

The UV X2200 signals a fault condition when less than half of the detection range remains. This is indicated by

the fault message on the EQP controller and is evident by the yellow color of the LED on the face of the detector.

The Oi feature is set to automatic as a factory default but can be deselected for “manual only” operation. Manual

Oi tests can be initiated via the detectors point display in the S

3

software.

Oi Test Frequency

The default Oi test frequency is once a minute but can be adjusted to any whole minute increment up to a

maximum of ten minutes.

Oi Test Fault

The detector automatically conducts Oi tests to check the integrity of the optical sensing systems. Three

consecutive failed Oi tests will generate a fault condition, which will be indicated by the LED on the face of the

detector turning yellow. The EQP Controller and S

3

software will also annunciate this fault. In certain environmental

conditions like very heavy rain, Oi test failures can occur even though the hardware is not faulty. To compensate

for this the number of failed Oi tests required to generate the fault can be adjusted upward to a maximum of 30.