12-62

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

Alarm Setpoints

The High and Low gas alarm setpoints can be changed by entering new values in the fields provided on the

dialog box.

The default values are 50% LFL for the High Alarm and 20% LFL for the Low Alarm.

The High alarm can be adjusted within a range of 5% LFL and 60% LFL.

The Low alarm can be adjusted within a range of 5% LFL and 40% LFL.

Note

the Low Alarm setpoint cannot be set to a higher value than the High Alarm setpoint.

PV Deadband

The “PV Deadband” field determines what percentage change in the Process Variable (PV) will prompt the unit

to send an immediate update to the controller instead of waiting for its regularly scheduled message time. The

default is 5%.

Common Settings

The bottom of the “PIRECL Editor...” dialog box contains buttons for setting all of the common settings on the

device.