11-14

EAGLE QUANTUM PREMIER CONFIG.

Version 6.0

EAGLE QUANTUM PREMIER CONFIG.

Diagnostic data is displayed to two ways on the display, through the color of the rectangle defining each node,

and through indicators and counters at the bottom of the screen.

The LON is typically wired as a loop

starting and ending at the controller

which has two physical interfaces

(transceivers) labeled “A” and “B”.

On an intact LON each of

these transceivers receives

information from all of the field

devices at roughly the same

time. A nodes proximity to one or the other transceiver along with the propagation delay of long wiring distances

and/or network extenders will induce a small time differential. This differential will cause an individual nodes

message to be read by either the A or B transceiver first and processed by the controller.

If the last message processed by the controller for a node comes through the “A” transceiver the rectangle

representing that node will have a green outline on the diagnostic LON schematic. If it comes through the “B”

transceiver its rectangle will be outlined in yellow.

Normal LON

On a healthy LON with good network integrity, message traffic will appear random and each nodes outline color

will constantly change without any pattern.

Faulted LON

On a faulty LON with a break in the wiring or other abnormal condition, message traffic may have only one path

to the controller. This would be indicated graphically by all of the nodes before the problem changing to one

color (green or yellow) and the nodes after the problem changing to the other color. The area where the color

transition occurs is most likely the problem area.

In this way the LON diagnostic display can be used to localize LON wiring problems. In addition to the graphic

representation of message traffic on the display, quantitative data is available for diagnostics through indicators and

counters.

If a node on the schematic is selected (by

single-clicking on its rectangle) the five

indicators in the lower left of the screen

will show the diagnostic data from the

selected node.

To the right of these indicators are LON counters that show message

processing by the controller. On a healthy system the counters should

be close to equal. On a system with a degraded network, there may be

a significant offset showing either the “A” or “B” transceiver getting the

majority of traffic.

Reset Module

To the right of the LON counters is the “Reset Module” button. This

command forces a selected field device to perform a “soft restart”

effectively “rebooting” the field device. This will also reset any latched

alarms, faults, outputs, etc.

COMMAND BAR • LON DIAGNOSTIC