12-22

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

Alarm LED Latch

The tri-color LED on the face of the detector turns red when in alarm and can be configured to be either latching

or non-latching. If latching is selected, following a fire detection, the LED will stay on until the detector is reset

from the point display for the detector in the S

3

software. The default is non-latching.

Fault LED Latch

The tri-color LED on the face of the detector turns yellow when a fault is present (fire over-rides fault) and can

be configured to be either latching or non-latching. If latching is selected, following a fire detection, the LED will

stay on until the detector is reset from the point display for the detector in the S

3

software. The default is non-

latching.

PV Deadband

A field is provided to enter the desired PV (Process Variable) Deadband.

Normally all values are transmitted to the controller every five seconds; If the PV changes more than the entered

percentage before the five second report time arrives, an immediate message is sent with the current values.

MIR H2 X3302 • ALARM LED LATCH