Eqp logic editor, Item 25 - beeper volume, Item 26 - channel type – Det-Tronics S3 Graphics User Manual
Page 295: Item 27 - low alarm latching, Item 28 - high alarm latching, Item 29 - dcu type code
13-70
EQP LOGIC EDITOR
Version 6.0
Item 25 - Beeper Volume
The volume level of the internal beeper can be adjusted with this variable. Values from 1 (lowest) to 4 (highest)
are allowed.
Beeper Volume
Value
Description
1
Off
2
Low
3
Medium
4
High
Item 26 - Channel Type
This variable is used to configure device channels. See Section EQ37EDIO-SIL for more details.
Value
Definition
1
Input
2
Output
3
Smoke Detector
4
Class A Output A (First of the pair)
5
Class A Output B (Second of the pair)
6
Class A Input A (First of the pair)
7
Class A Input B (Second of the pair)
8
Solenoid Output
9
Class A Solenoid Output A (First of the pair)
10
Class A Solenoid Output B (Second of the pair)
11
Class A Smoke Input A (First of the pair)
12
Class A Smoke Input B (Second of the pair)
Item 27 - Low Alarm Latching
When this configuration variable is set low alarms are latched until the unit is power cycled or a reset command
is issued.
Item 28 - High Alarm Latching
When this configuration variable is set high alarms are latched until the unit is power cycled or a reset command
is issued.
Item 29 - DCU Type Code
See the DCU section for a description of this variable.
DEVICE ITEM NUMBER DESCRIPTIONS