EAGLE QUANTUM PREMIER DEVICES

12-37

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Oi Mode

The UVIR X5200 includes the Automatic Optical Integrity (Oi) feature — a performance test that is automatically

performed to verify complete detector operation capabilities.

Combined Settings

The bottom portion of the dialog box contains settings for the alarm latching, Optical Integrity (Oi), input time

delay and PV deadband adjustments that apply to the whole detector as opposed to a specific sensor.

Alarm Latching Mode

The red LED on the face of the detector comes on when in alarm and can be configured to be either latching or

non-latching. If latching is selected, following a fire detection, the LED will stay on until the detector is reset from

the point display for the detector in the S

3

software. The default is non-latching.

Time Delay

An input time delay can be programmed by entering a value from 1 to 15 seconds in the provided field. This will

delay sending the fire alarm message to the EQP controller until the fire alarm has been generated uninterrupted

for the specified time. This programmable delay can be used to filter out spurious events.

PV Deadband

A field is provided to enter the desired PV (Process Variable) Deadband. Normally all values are transmitted to

the controller every five seconds; If the PV changes more than the entered percentage before the five second

report time arrives, an immediate message is sent with the current values.

X5200 • ALARMS