Signal Audible Module (SAM)

The EQ2500SAM Signal Audible Module is located on the LON/SLC and provides NFPA-72 compliant Notification

Appliance Circuit (NAC) control capability to the Eagle Quantum Premier system.

The Signal Audible Module provides two indicating circuits for controlling UL Listed 24 Vdc polarized audible/

visual indicating appliances.

The device is located on the LON and is controlled by programmable logic in the Controller.

Each output circuit is independently programmable to allow notification of separate events.

Each output can be individually activated for any one of the following pre-defined outputs:

Continuous

1.

60 beats per minute

2.

120 beats per minute

3.

Temporal pattern.

4.

Device outputs operate in the reverse polarity manner when activated. Each output is rated at 2 amperes.

The output circuits are supervised for open and short circuit conditions.

If a wiring fault occurs, a trouble condition will be indicated at the Controller and on the S

3

Point Display.