Oi mode, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 164

Advertising
background image

EAGLE QUANTUM PREMIER DEVICES

12-49

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Alarm Latching Mode

The red LED on the face of the detector comes on when in alarm and can be configured to be either latching or

non-latching. If latching is selected, following a fire detection, the LED will stay on until the detector is reset from

the point display for the detector in the S

3

software. The default is non-latching.

Oi Mode

The UV EQ2200 includes the Automatic Optical Integrity (Oi) feature — a performance test that is automatically

performed once per minute to verify complete detector operation capabilities. No testing with an external test

lamp is required. The detector automatically performs the same test that a maintenance person with a test

lamp would perform —once every minute, 60 times per hour. However, a successful automatic Oi test does not

produce an alarm condition. The UV EQ2200 signals a fault condition when less than half of the detection range

remains. This is indicated by the Oi fault message on the EQP Controller and via the S

3

software. The default

mode is Automatic. Manual Oi tests can be initiated from the point display in the S

3

software.

Time Delay

An input time delay can be programmed by entering a value from 1 to 7 seconds in the provided field. This will

delay sending the fire alarm message to the EQP controller until the fire alarm has been generated uninterrupted

for the specified time. This programmable delay can be used to filter out spurious events.

EQ2200UV • ALARM LATCHING