Eqp logic editor – Det-Tronics S3 Graphics User Manual

Page 314

Advertising
background image

13-89

EQP LOGIC EDITOR

Version 6.0

Item 254 - Missed Messages

The number of times that an incoming packet was discarded because there was no network buffer available.

Item 255 - IR Processing Mode

This item is used to select the processing mode for the IR detector.

Value

Description

1

TDSA

3

TDSA and Quick

Item 256 - UV Auto Oi Test Frequency

This item is used to select how often the automatic Oi test is conducted, see the device for the allowable range.

Item 257 - IR Auto Oi Test Frequency

This item is used to select how often the automatic Oi test is conducted, see the device for the allowable range.

Item 258 - Consecutive UV Failed Oi Tests for Fault

This item is used to select how many consecutive automatic Oi tests must fail before a fault is annunciated.

Item 259 - UV Counts per Second

This item will display the UV signal level.

Item 260 - IR Signal Level

This item will display the IR signal level.

Item 261 - TDSA IR Alarm

This item comes true when the IR detector generates a TDSA fire alarm.

Item 262 - UV Pre Alarm

For the new flame platform detectors, this item comes true when the number of UV counts per second exceeds

½ of that needed to signal an alarm.

Item 263 - IR Pre Alarm

For the new flame platform detectors, this item comes true when 18 or more valid turning points are found during

a 10 second period.

Item 264 - UV Oi Calibration Active

This item comes true while the UV Oi calibration is active.

Item 265 - IR Oi Calibration Active

This item comes true while the IR Oi calibration is active.

Item 266 - UV Oi Fault

This item comes true when a manual or automatic UV Oi fault occurs.

Item 267 - IR Oi Fault

This item comes true when a manual or automatic IR Oi fault occurs.