EQP LOGIC EDITOR

Version 6.0

Item 222 - Request Temperature

Setting this control bit will cause the controller to retrieve the temperature from a device.

Item 223 - Heater Enable Control

This item is used to control the optics heater from user logic. This allows the user to disable the heater when AC

power is lost.

Item 224 to 239 - User Parameters 1-16

User parameters can be used as part of a self configuration process. The values are saved in flash memory

when program mode is exited.

Item 240 - Start Manual Oi Fire Test

Setting this control bit will instruct the flame detector to conduct an Oi test and activate the fire alarm output if the

unit passes the test. This feature must be password protected.

Item 241 - Sustained Fire

A field device sets this status bit to indicate that it has detected a sustained type fire. In the X3301 this is the

ORED status of Bin fire, low level fire, and non-ratio fire bits.

Item 242 - Lon CPU Memory Fault

A field device sets this status bit to indicate that it has detected a problem with the memory used with the LON

CPU.

Item 243 to 247 - New Alarms

The bit is set for one scan of logic when new alarms occur. Intended for resounding silenced alarms in user

logic.

Item 248 - Install Network Extender

Setting this control item instructs the controller to request the network extenders neuron Ids. The Ids are used to

address the device when getting network diagnostic information. The neuron Ids will be retained in flash memory

when program mode is exited.

Item 249 - Request Lon Diagnostic Info

Setting this control item instructs the controller to request the Lon Diagnostic Information from the device. Items

250 to 254 are updated.

Item 250 - Transmission Errors

The number of CRC errors detected during packet reception. These may be due to collisions or noise on the

transceiver input.

Item 251 - Transaction timeouts

The number of times that the node failed to receive expected acknowledgements or responses after retrying the

configured number of times. These may be due to the destination node being offline.

Item 252 - Rcv Transaction Full

The number of times that an incoming packet was discarded because there was no room in the transaction

database.

Item 253 - Lost Messages

The number of times that an incoming packet was discarded because there was no application buffer

available.