12-16

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

Alarm LED Latch

The tri-color LED on the face of the detector turns red when in alarm and can be configured to be either latching

or non-latching. If latching is selected, following a fire detection, the LED will stay on until the detector is reset

from the point display for the detector in the S

3

software. The default is non-latching.

Fault LED Latch

The tri-color LED on the face of the detector turns yellow when a fault is present (fire over-rides fault) and can

be configured to be either latching or non-latching. If latching is selected, following a fire detection, the LED will

stay on until the detector is reset from the point display for the detector in the S

3

software. The default is non-

latching.

Detector Sensitivity

The sensitivity of the detector can be adjusted between medium and very high using the sensitivity slider control

in the center bottom area of the configuration dialog box.

MIR X3301 • ALARM LED LATCH