Eqp logic editor – Det-Tronics S3 Graphics User Manual

Page 302

Advertising
background image

13-77

EQP LOGIC EDITOR

Version 6.0

Item 79 - CPU Fault

The item indicates a problem with a processor or memory system, the cause of this fault is device dependent.

Item 80 - Supervisory

This item tracks the state of the controller Supervisory LED and relay, if programmed for the alternate function.

Item 81 - Channel Active

This item tracks the state of an I/O channel.

Item 82 - Control Message Fault

This item is set when a field device does not receive the output control message from the controller.

Item 83 - Channel Shorted

This item indicates when an I/O channel is shorted.

Item 84 - Channel Open

This item indicates when an I/O channel is open.

Item 85 - Channel Isolated

This item indicates when an I/O channel is isolated.

Item 86 - Normalized Process Variable

Normalized process variable holds the analog value read from the device as a floating point value. For devices

with adjustable ranges, values are calculated by using the zero and full scale range values.

Item 87 - Raw Process Variable:

Raw process variable holds the analog value read from the device as an integer value. For devices with adjustable

ranges, values are calculated by using the zero and full scale range values. When the raw integer format is used

values are in the range of 0 to 4095. Values for an ideal 4 to 20 mA sensor are:

DCU Process Variable

Input

Output

0 mA

0

4 mA

682

12 mA

2048

20 mA

3413

24 mA

4095

Item 88 - AC Voltage

The AC voltage can be read with this variable.

Item 89 - Temperature

The temperature in degrees C can be read with this variable.

Item 90 - Battery Current

This variable represents the battery charge or discharge current level. Positive values indicate battery charging

while negative values represent battery discharge.

DEVICE ITEM NUMBER DESCRIPTIONS

DEVICE ITEM NUMBER DESCRIPTIONS