Eagle quantum premier config – Det-Tronics S3 Graphics User Manual

Page 90

Advertising
background image

EAGLE QUANTUM PREMIER CONFIG.

11-9

EAGLE QUANTUM PREMIER CONFIG.

Version 6.0

Once the event name is entered and the comparison

configured, the event tracking configuration is set up using

the check boxes and menus to the right of the event name.

The five checkbox selections are defined below:
P: Printer (Tractor feed event printer)
D: Disk (Daily log file)
W: Window (One line FIFO display)
AC: Auto Clear (Event directly tracks the “raw” data state and

doesn’t require operator acknowledgement)
FL: Fault (Designates the event to be considered a fault

instead of an alarm).

In the completed sample

above, when the analog

value exceeds 29 the event

“30 Seconds Remaining”

will be logged to the printer

(in red), daily log file, event

window and the OIS will play

the “Warning” sound.

When the value drops below

29 the event will automatically

clear.

Selecting a “Monitored Global” display its associated configuration data in the “Configuration” pane to the right

of the globals list.

This provides “at a glance” a complete configuration overview of the selected global.

COMMAND BAR • GLOBALS