EAGLE QUANTUM PREMIER DEVICES

12-51

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

User Levels

The “User Level Editor...”

provides a means for limiting

access to the “Acknowledge”,

“Remove”, “Manual Oi”, “Inhibit”, Manual Oi (FIRE)” and “Reset”

buttons for the module which are accessible from the devices point

display. The default value is “0” and provides access to all users.

Change these values to match a user account configuration and

security needs.

Point Display

The UV EQ2200 has a custom “Point Display” that can be accessed

from either the Point Display button on the Command Bar or from the Online Mode. The point display provides a

single window view of all available real-time data for the device.

Alarm Logs
The top right quadrant of the display shows the last eight alarms with their date and time data.

Analog Input Track
The top left quadrant shows a dynamic 60 second history of the measured variable (UV counts) for the detector.

The input track scrolls from left to right with the most current data at the “pen” on the left margin. The display

updates once every five seconds.

Status & Diagnostics
The middle portion of the point display shows the discrete status and health indicators for the detector.

Buttons
There are four buttons that can send commands to the detector including; Remove, Inhibit, Reset and Manual Oi.