Eqp logic editor – Det-Tronics S3 Graphics User Manual

Page 243

Advertising
background image

13-18

EQP LOGIC EDITOR

Version 6.0

EQP LOGIC EDITOR

In the example to the right, the “LON” item has been expanded by

clicking on the “+” sign and now shows ten subordinate items, each of

which is a field device.

As these additional items are revealed, the list extends beyond the

bottom and becomes scrolling.

The hierarchical arrangement of items provides an easy and logical

method of accessing the thousands of potential items that could be

configured as outputs on a large premier system.

In the example below, a field device on the LON, an UVIR Fire Detector

with the tagname “UVIR-013” has been selected and “opened” to display

its subordinate data. Any of the displayed items can be selected and

configured for “movement” to the MB system utilizing the “drag and

drop” method.

To configure a data point for

“movement” click and “drag” the

selected point to the right side of

the dialog box and “drop” it on

the desired Modbus destination

address.

In the above example, the “Fire

Alarm” point is in the process

of being moved to the selected

destination address “40001/1” in

the MB table.

Once “dropped” in the desired cell

in the “Source” column on the right side of the dialog box, the “Fire Alarm” status for “UVIR-013” will now map to

the first “bit” of register 40000, Modbus destination address of “40001/1”.

This process must be

repeated for all data to be

shared with the MB host

device.

LOGIC EDITOR • CONTROLLER MENU

Advertising