EQP LOGIC EDITOR

Version 6.0

Item 295 - Smoke Detector Type

This item selects a type of smoke detector.

Value

Detector Type

0

Invalid

1

Apollo

2

Fenwal

Item 296 - Abort Mode

This item selects the type of abort mode.

Value

Mode

0

Invalid

1

Mode 1

2

Mode 2

3

IRI Mode

Mode 1:

Upon activation, timer will count down to and hold at 10 seconds; upon release, timer will continue to

count down to zero.

Only this mode complies with UL 864.
Mode 2:

Upon activation, timer will reset to initial value; upon release, timer will continue to count down to zero.

IRI Mode:

This function is similar to “Mode 1” with the exception that the abort will only function if held prior to

receiving the second alarm.

Item 297 - Detection Style

This item selects the Detection Style – Single or Cross Zoned. When single zone is selected, a release is activated

if ether input is activated. Cross zone requires that both inputs be active before a release is activated.

Value

Mode

0

Invalid

1

Single Zone (1 zone

release)

2

Cross Zoned (2 zone

release)