Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual
Page 169
12-54
EAGLE QUANTUM PREMIER DEVICES
Version 6.0
EAGLE QUANTUM PREMIER DEVICES
Tagname
The tagname at the top of the dialog box refers to the flame detector as a whole and is the identifier used for
programming.
Until a tagname is entered the detector is not available in the S
3
database for programming, monitoring or
dynamic graphic purposes. The optional description entered in the miscellaneous text field can be used for
further describe where or how the detector is being used and can be helpful in troubleshooting.
Sensor Settings & Sensitivity
Both the UV and IR sensors have independently adjustable settings for a variety of processing and sensitivity
variables that can be used to fine tune the detectors operation to fit the application.
UV Specific Settings
The UV flame detector can be programmed for either “Standard Signal Processing” or “Arc Rejection”.
Arc Rejection (Recommended Factory Setting)
The Arc Rejection mode enables the detector to prevent nuisance fire alarms caused by UV from short-duration
electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect the UV given off by a
flame. Most false alarm sources have short transient UV signatures, while fire creates a long UV signature over
many seconds. Most fires are detected in a few seconds.
EQ2200UVIR • CONFIGURATION