Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 169

Advertising
background image

12-54

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

Tagname

The tagname at the top of the dialog box refers to the flame detector as a whole and is the identifier used for

programming.

Until a tagname is entered the detector is not available in the S

3

database for programming, monitoring or

dynamic graphic purposes. The optional description entered in the miscellaneous text field can be used for

further describe where or how the detector is being used and can be helpful in troubleshooting.

Sensor Settings & Sensitivity

Both the UV and IR sensors have independently adjustable settings for a variety of processing and sensitivity

variables that can be used to fine tune the detectors operation to fit the application.

UV Specific Settings

The UV flame detector can be programmed for either “Standard Signal Processing” or “Arc Rejection”.

Arc Rejection (Recommended Factory Setting)

The Arc Rejection mode enables the detector to prevent nuisance fire alarms caused by UV from short-duration

electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect the UV given off by a

flame. Most false alarm sources have short transient UV signatures, while fire creates a long UV signature over

many seconds. Most fires are detected in a few seconds.

EQ2200UVIR • CONFIGURATION