EQP LOGIC EDITOR

Version 6.0

Item 352 - Controller Inhibit Mode

In Alarms only mode, the inhibit feature inhibits only the alarms. The Alarms and Fault Mode inhibits all faults that

trigger the Controller fault relay as well as alarms. The Alarms and Fault Mode also complies with EN54.

Control Inhibit Mode

Value

Mode

1

Alarms Only

2

Alarms & Faults (EN54)

Item 353 - Controller Fault

This fault LED is set when the Controller is reset due to a Watch Dog Reset. It may only be cleared by a power

cycle.

Item 354 - TX Lamp Fault

This Open path fault is set when the receiver has determined that the transmitter is flashing in the fault mode.

This mode indicates that the transmitter lamp B is currently active.

Item 355 - Beam Block

This Open Path receiver has been blocked of all flash events.

Item 356 - ADC Saturation

This Open Path receiver and receiver are too close together.

Item 357 -Cal Active at Start

This fault is active when the switch input, which is pin 13 on the terminal board, is closed during power up. This

fault is not active for a reed switch closure at startup.

Item 358 - Noise fault

This is an interference fault. It does not typically occur by itself.

Item 359 - Channel Fault Warning

This is a fault that is associated with each channel of a multi-channel field device. This is activated when there

is any fault that affects the channel. The channel may or may not function. This only applies when the Controller

Inhibit Mode is set to Fault Inhibit.

Item 360 - Gas Diode Gain

This is the current setting of the programmable amplifier used for the Open Path gas sensors. The setting may

be a value from 1 through 7.

DEVICE ITEM NUMBER DESCRIPTIONS