Eqp logic editor – Det-Tronics S3 Graphics User Manual

Page 304

Advertising
background image

13-79

EQP LOGIC EDITOR

Version 6.0

Item 102 - LON B Interface Fault

The bit is set when a problem is detected with LON interface channel B.

Item 103 - Inhibit Status

This item is set when a device or channel has been inhibited.

Item 104 - Zero Drift

This item is set when a gas detector goes negative to point of a fault.

Item 105 - Option Board Fault

The controller sets this item true when a fault is detected in the controller option board.

Item 106 - Invalid Configuration

This item is set on new units, when the address is changed, or when invalid data is transferred to the device. A

valid configuration must be downloaded to clear the item.

Item 107 - Fault

The controller performs a logical OR of all field device faults to control this item.

Item 108 - Unable to Configure

This item is set when the controller is unable to successfully transfer configuration information to the field

device.

Item 109 - Last Direction

The controller has two LON channels A and B. In normal operation, both channels receive status messages

from all devices. However, during network fault conditions messages will only be received from one side. This

item indicates the last side status information was received from. This along with the offline bits can be used in

determining the location of a network break. When the bit has a value of 0, channel A was the last side, a value

of 1 indicates channel B was the last side.

Item 110 - Lon A Device Offline

This item is set when the controller has not recently received status messages from the device on the first Lon

channel.

Item 111 - Lon B Device Offline

This item is set when the controller has not recently received status messages from the device on the second

Lon channel.

Item 112 - Device Offline

Three offline item are provided for enhanced fault diagnostics. The controller maintains offline timers for every

device on the network. The controller sets the LON x device offline item when it has not received messages from

the device on that channel, A or B. The device offline fault item is set when both LON A and B offline bits are set

(totally offline). The controller will not attempt to talk to devices that are offline. The item are automatically cleared

when status messages are received.

DEVICE ITEM NUMBER DESCRIPTIONS

DEVICE ITEM NUMBER DESCRIPTIONS

Advertising