Configuration, Alarms, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 211

Advertising
background image

12-96

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

Description

This field provides an area to describe the function of each relay. Adding this optional information can make

troubleshooting and startup easier.

Com Fail Mode

Each of the 8 relays can be individually configured to respond in one of three ways in the unlikely event of a

complete loss of communications with the EQP controller.

The three selections are as follows:

Failed Off

:

Relay coil de-energizes

Failed On

:

Relay coil energizes

Hold Last State

: Relay coil stays energized or de-energized as per its last valid command from the EQP

controller.

Alarms

Selecting this button opens the “Alarms to Monitor...” dialog box.

This scrolling list displays the alarms and events related to the device that can be configured to be monitored

by S

3

.

RELAY MODULE • COM FAILED MODE

Advertising