Eqp logic editor – Det-Tronics S3 Graphics User Manual

Page 300

Advertising
background image

13-75

EQP LOGIC EDITOR

Version 6.0

Item 54 - Calibration Gas Type

Calibration gas type is selected with this code.

Description

Mode

Same as Measured (Default)

1

Methane

2

Propane

3

Item 55 - Calibration Method

Description

Code

Standard (Default)

1

Cuvett

2

Item 56 - Cuvett Length

1.0 to 150.0 mm, default 150mm

Item 57 - Calibration Gas Concentration

The allowable range is from 20 to 100% with 50% as the default.

Item 58 - Volume at LFL

Used for programming a special gas type, the default value is 5%.

Item 59 - Gas Coefficient a

Used for programming a special gas type.

Item 60 - Gas Coefficient b

Used for programming a special gas type.

Item 61 - Gas Coefficient c

Used for programming a special gas type.

Item 62 - Gas Coefficient d

Used for programming a special gas type.

Item 63 - Gas Coefficient e

Used for programming a special gas type.

Item 64 - Device Removed

The user sets this bit when the device has been removed from the system. Configuration information shall be

retained in the controller to allow the device to be added at a later time. If the removed bit is set when program

mode is exited, the status will be saved during a power cycle.

This item is used to tell the controller a device has been removed from the network. The controller will signal the

“Extra LON Device” fault if the device is on-line with the removed item is set.

Item 65 - Static Logic Inverted

Setting this item tells the controller invert the signal when used with-in static logic. This can be used to have a

normally energized controller relay or a normally active digital input.