Point display, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 146

Advertising
background image

EAGLE QUANTUM PREMIER DEVICES

12-31

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Point Display

The IR X9800 has a custom “Point Display” that can be accessed from either the Point Display button on the

Command Bar or from the Online Mode. The point display provides a single window view of all available real-time

data for the device.

Alarm Logs
The top right quadrant of the display shows the last eight alarms with their date and time data.

Analog Input Track
The top left quadrant shows a dynamic 60 second history of the measured variable (IR counts) for the detector.

The input track scrolls from left to right with the most current data at the “pen” on the left margin. The display

updates once every five seconds.

Manual Oi Log
The bottom left quadrant of the point display shows the detectors manual Optical Integrity (Oi) log. The last eight

manual tests are shown with the date, time and a PASS/FAIL indicator.

Status & Diagnostics
The middle portion of the point display shows the discrete status and health indicators for the detector.

Buttons
There are six buttons that can send commands to the detector including; remove, inhibit, reset, Manual Oi,

Manual Oi (FIRE) and IR Calibration.

X9800 • ALARM LOGS

Advertising
This manual is related to the following products: