Item 91 - Flame Detector Counts per Second

This variable represents the counts per second from flame detectors.

Item 92 - Supply Voltage

Field device supply voltage as measured at the device can be read with this item.

Item 93 - Wrong Device Type

This item is reserved to signal that the controller has detected a wrong device type (Not supported in the first

release).

Item 94 - Extra LON Device

This item is used to signal that the controller has detected an extra device on the LON.

Item 95 - Logic Error Reference Number

If the controller detects an error in user logic, the last trace number is stored in this item.

Item 96 - Logic Error Code

If the controller detects an error in user logic, an error number is stored in this item.

Logic Error Code

0

No Error

1

Unknown Instruction Type

2

Unsupported Address Mode

3

Unsupported Data Type

4

Unsupported Instruction

5

A parameter error was detected

6

Too many items on the stack for this opera-

tion

7

User Program is too large

8

First Scan Program Too Large to Complete

9

Initial CRC was Incorrect

10

Failed Background CRC test

11

Instruction Pointer Error

Item 97 - Memory Fault

When this item is true, a fault has been detected in the memory system.

Item 98 - RTC Fault

When this item is true, the real time clock needs to be set, or the clock circuitry has malfunctioned.

Item 99 - LON Ground Fault

When this item is true, the controller has detected a ground fault.

Item 100 - Duplicate Address

Not supported.

Item 101 - LON A Interface Fault

This bit is set when a problem is detected with LON interface channel A.