Intelligent protection module (ipm), Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 196

Advertising
background image

12-81

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Intelligent Protection Module (IPM)

8 channel input/output module for 24 Vdc discrete field devices

The Intelligent Protection Module (IPM) is a part of the Det-Tronics Eagle Quantum Premier (EQP) System that is

specially designed to monitor, supervise and control one fire suppression hazard.

The IPM is designed to provide continuous and automated local area fire protection, while monitoring system

operation through continuous supervision of its Inputs/Outputs and Local Operating Network/Signalling Line

Circuit (LON/SLC) connection to the EQP controller.

In addition the module contains a unique “embedded logic program” that if enabled during configuration allows

the IPM to perform local area protection in a “back-up mode” without controller interaction. The IPM utilizes eight

pre-configured Input/Output (I/O) channels to perform its monitoring, supervision and mitigation functions.

Inputs

On the input side, three supervised channels provide the following connections:

Channel 1 for an Abort station

Channel 2 for a Manual Release station

Channel 3 for a Supervisory device.


Two additional input channels (zones) provide connections for “two-wire” conventional (non-relay based) smoke

and heat detectors.

Channel 4: Zone 1 detection circuit

Channel 5: Zone 2 detection circuit

Outputs

On the output side, three supervised outputs (1 signaling, 2 releasing) provide the following connections:

Channel 6 for a notification appliance such as a bell, horn or lamp.

Channels 7 & 8 for a main and reserve or secondary agent release.

INTELLIGENT PROTECTION MODULE (IPM)

Advertising
This manual is related to the following products: