Point Display

The Open Path Eclipse has a custom “Point Display” that can be accessed from either the Point Display button

on the Command Bar or from the Online Mode.

The point display provides a single window view of all available real-time data for the device.

Input Tracking

The upper left quadrant contains a 60 second analog track running from left to right, the newest data on the left

margin. This area graphically displays the low and high alarm setpoints as horizontal lines crossing the graph

area, Yellow for High and Orange for Low. Digital readouts at the lower margin also display the PV and alarm

setpoints.

Alarm History

The upper right quadrant displays the alarm history for the device. The last eight alarms with date and time are

shown. This data is stored in the field device and retrieved over the LON for display.

Calibration History

The lower left quadrant displays the calibration history for the device. The last eight calibrations with date and

time are shown. This data is stored in the field device and retrieved over the LON for display.

Temperature

The lower right quadrant displays the sensor package temperature.

Status & Diagnostics

Crossing the whole point display in the center is an area displaying 24 discrete pieces of status and diagnostic

information on the detector.