Eqp logic editor – Det-Tronics S3 Graphics User Manual
Page 307
13-82
EQP LOGIC EDITOR
Version 6.0
A device sets this item to indicate that the optics need to be cleaned.
Item 142 - Internal Comm Fault
A device sets this item to indicate that a fault has occurred in the communications between the LON and host
processors.
Item 143 - Warm-up
A device sets this item during the warm-up period.
Item 144 - Open Lamp
A device sets this item to indicate an open lamp fault.
Item 145 - Alarm Logs
Up to 8 alarm logs are held in this item.
Item 146 - Calibration Logs
Up to 8 calibration logs are held in this item.
Calibration Log Format
Description
Data Type
Seconds
Int
Minutes
Int
Hours
Int
Day
Int
Month
Int
Year
Int
Zero Reading
Int
Span Reading
Int
Item 147 - Activate Output
Setting this control item will activate the output.
Item 148 - Reset Application
Setting this control item will reset the device application program.
Item 149 - Request Supply Voltage
Setting this control item instructs the controller to retrieve the input voltage from the field device.
DEVICE ITEM NUMBER DESCRIPTIONS