Eqp logic editor – Det-Tronics S3 Graphics User Manual

Page 310

Advertising
background image

13-85

EQP LOGIC EDITOR

Version 6.0

Item 165 - Activate Low Gas Alarm

Setting this control item in the controller activates the low gas alarm output.

Item 166 - Activate High Gas Alarm

Setting this control item in the controller activates the high gas alarm output.

Item 167 - LON A Counter

Within the controller object, this status variable holds the number of heartbeat messages received. Resetting

the controller will also reset this counter. When this variable is used with a field device it shows the number of

received status messages. The counters are helpful for diagnosing wiring problem on the Lon network.

Item 168 - LON B Counter

Within the controller object, this status variable holds the number of heartbeat messages received. Resetting

the controller will also reset this counter. When this variable is used with a field device it shows the number of

received status messages. The counters are helpful for diagnosing wiring problem on the Lon network.

Item 169 - Display Text Line 1

This variable holds the ASCII test string on the controller faceplate.

Item 170 - Display Text Line 2

This variable holds the ASCII test string on the controller faceplate.

Item 171 - Display Text Line 3

This variable holds the ASCII test string on the controller faceplate.

Item 172 - Display Text Line 4

This variable holds the ASCII test string on the controller faceplate.

Item 173 - Heater Enable Status

This item is true when the Optics heaters are enabled. They may or may not actually be on at the time depending

on the temperature.

Item 174 - LON Fault

The controller sets this item when a Lon fault is detected.

Item 175 - Signal to Noise Ratio

A detector’s signal to ratio is held in this variable.

Item 176 - Activate Silence

Setting this control bit activates the controller silence status bit and LED. The LED and status bit will stay true until

the controller is reset. The controller clears this control bit after the action is taken.

Item 177 - Activate Acknowledge

Setting this control bit activates the controller acknowledge status bit, LED, and silences the internal beeper. The

LED and status bit will stay true until the controller is reset. However, the beeper will resound if new alarms are

received. The controller clears this control bit after the action is taken.

Item 178 - Start IR Oi Calibration

Setting this control bit will cause the controller send a start IR Oi calibration message to the field device. The

controller clears this control bit after the action is taken.

DEVICE ITEM NUMBER DESCRIPTIONS

DEVICE ITEM NUMBER DESCRIPTIONS