EQP LOGIC EDITOR

13-17

EQP LOGIC EDITOR

Version 6.0

Tab 1

Is for “Coils” which typically represent “Outputs” in a Modbus PLC. Coil

addresses start with “0”.

Tab 2

Is for “Inputs” which typically represent discrete input cards in a

Modbus PLC. Input addresses start with “1”.

Tab 3

Is for registers (16 bit words) that occupy an address range

beginning with 40,001.

Registers can be used either as a whole “16 bit” word

to move an integer value, or as sixteen individual “bits”,

into which boolean “ON/OFF” data can be moved.

When the “All to MB” tab is selected, a hierarchical

list of “sources” is shown on the left hand side of the

dialog box which can be selected for “movement” to

“destinations” in the AB system.

Any item on the list that has a “+” before it has

subordinate items and clicking on the “+” will expand

the list showing all items that make up that category.

Below the list are two buttons that can “Expand” or

“Collapse” all subordinate items in the list for easy

viewing.

The firsts twelve items on the list provide access

to controller status information and the globals

database.

The “LON” item will allow access to all field device

information, the “Relays” item is for accessing the

controllers onboard relay status.