13-101

EQP LOGIC EDITOR

Version 6.0

Item 361 - Beam Block Delay

The beam block delay is used with Open Path. This is the amount of time that must go by before a blocked beam

fault is declared. The delay is configurable from 1 minute to 60 minutes.

Item 362 - Standby Power Fault 1

The standby controller sets this status variable when low voltage is detected on the power input #1.

Item 363 - Standby Power Fault 2

The standby controller sets this status variable when low voltage is detected on the power input #2.

Item 364 - Standby LON Fault

The standby controller sets this item when a Lon fault is detected.

Item 365 - Standby LON Gnd Fault

When this item is true, the standby controller has detected a ground fault.

Item 366 - Standby Controller Fault

This item is true when the standby controller has been reset by a Watch Dog Reset.

Item 367 - HSSL Communication Fault

This item is true when the master controller loses communication with the standby controller.

DEVICE ITEM NUMBER DESCRIPTIONS