13-99

EQP LOGIC EDITOR

Version 6.0

Item 343 - Suppression Timer

First used with the Automotive MIR Flame Detector (X3301). Refer to the AMIR X3301 specification for details on

this parameter.

Item 344 - LON Diagnostic Fault

This is a new fault used by SIL field devices. The controller will issue this fault when the percent of missed status

messages from a device is greater than 10% from both channels.

Item 345 - SIL Device

When this config bit is set it tells the Controller or field device that it should have compliance with IEC61508 (SIL2)

operation. Controllers are configured with the factory test fixture for SIL operation. When the Controller is set for

SIL operation extra diagnostics are performed on an ongoing basis. The controller will signal the “wrong device

type” if the factory configuration does not match the configuration setting downloaded from S

3

.

Item 346 - Internal Voltage Fault

This fault bit is set when hardware diagnostics detects a problem with one of the internal power supplies. First

used with the EDIO-SIL device.

Item 347 - Hardware Fault

This fault bit is set when hardware diagnostics detects a hardware related problem. First used with the EDIO-SIL

device.

Item 348 - PWM Fault

This fault bit is set when hardware diagnostics detects hardware problem with the PWM (Pulse Width Modulator).

First used with the EDIO-SIL device.

Item 349 - Rogue Device

This fault bit is set when the controller detects two devices at the same address.

Item 350 - LON Pattern Test

This fault bit is set when the LON pattern message is incorrect or missing.

Item 351 - Watch Dog Timer Fault

This fault bit is set when the power-up test detects that the watchdog timer is not working properly.