EQP LOGIC EDITOR

Version 6.0

Item 49 - IR Oi Test Frequency

Three consecutive failures are required to fault, and three consecutive good tests are required to return to normal.

While an IR oi fault is active the test frequency is reduced to once per minute.

IR Oi Test Frequency

Value

Definition

1

1 minute (Default)

2

1 Hour

3

2 Hours

4

4 Hours

Item 50 - Full Scale Value

The Engineering unit full scale value can be configured and must match the current rating of power supply

monitor. Only one model has been defined, 80 Amp, with a range of -16 Amps to +80 Amps.

Item 51 - AC Fault Threshold

The power supply monitor fault threshold can be set with this variable.

Item 52 - Supervision Option Select

An I/O channel can be configured with or without supervision.

Mode

Definition

1

No Supervision

2

Monitor for opens

3

Monitor for opens and shorts

Item 53 - Eclipse Gas Type

This field allows the PIRECL to be configured for different gas types.

Code

Description

1

Methane (Default)

2

Ethane

3

Propane

4

Ethylene

5

Propylene

6

Butane

7

Reserved

8

Reserved

9

Reserved

10

Special

DEVICE ITEM NUMBER DESCRIPTIONS