Eqp logic editor, Item 43 - oi mode, Item 44 - latching – Det-Tronics S3 Graphics User Manual

Page 298: Item 45 - arm output mode, Item 46 - activation time, Item 47 - ir sensitivity, Item 48 - ir oi threshold, Device item number descriptions

Advertising
background image

13-73

EQP LOGIC EDITOR

Version 6.0

Item 43 - Oi Mode

Optical Integrity mode can be selected with this variable.

Oi Mode

Value

Definition

0

Automatic

1

Manual

Item 44 - Latching

0 = non-latching output.

1 = latching output.

Item 45 - ARM Output Mode

See the ARM section for a description of this variable.

Item 46 - Activation Time

The output hold on time can be set with this variable.

Item 47 - IR Sensitivity

The IR for UVIR flame detectors always uses 0.125 second gate length for sampling the counter. The signal is

compared to the threshold 0.5 second.

IR Sensitivity

Value

Definition

UV/IR

X3301

Counts per gate

Effective counts per second

1

Low

8

64

Low (not used)

2

Medium (default)

6

48

Medium

3

High

4

32

High (not used)

4

Very High

2

16

Very High (Default)

Item 48 - IR Oi Threshold

The Oi test will run for a maximum of five seconds.

IR Oi Threshold

Value

Definition

Counts per Second

1

Low

64

2

Medium (Default)

48

3

High

32

4

Very High

16

DEVICE ITEM NUMBER DESCRIPTIONS