Alarm setpoints, Pv deadband, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 182

Advertising
background image

EAGLE QUANTUM PREMIER DEVICES

12-67

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Alarm Setpoints

The High and Low gas alarm setpoints can be changed by entering new values in the fields provided on the

dialog box.

The default values are 2% LFLM for the High Alarm and 1% LFLM for the Low Alarm at a full scale of 5.00 LFLM.

The High and Low alarms can be adjusted within a range of 0.25% LFL and 3% LFLM.

Note

the Low Alarm setpoint cannot be set to a higher value than the High Alarm setpoint.

PV Deadband

The “PV Deadband” field determines what percentage change in the Process Variable (PV) will prompt the unit

to send an immediate update to the controller instead of waiting for its regularly scheduled message time. The

default is 5%.

Common Settings

The bottom of the “OPECL Editor...” dialog box contains buttons for setting all of the common settings on the

device.

OPECL • ALARM SETPOINTS