12-86

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

Controller Only

In this mode the I/O of the IPM will be controlled from the EQP Controller only and embedded logic is inactive.

Back-up Mode

The default selection) the IPM I/O is normally controlled by the EQP Controller but utilizes embedded logic in

accordance with the “Control Transfer Sequence Description” to control its I/O under certain circumstances.

Embedded Only

In this mode the IPM continuously operates from its embedded logic. The status of all IPM I/O is available to the

EQP Controller but control of the outputs are not; however, controller and S

3

reset commands are accepted.

Detection Circuit Delay Selection

This selection provides a time delay that will apply to the two detector circuits, (Channels 4 and 5) as well as to

the manual release signal (Channel 2).

There are seven time delay selections running between 0 and 60 seconds in ten second increments as shown

below:







0

Second

10

Seconds

20

Seconds

30

Seconds

40

Seconds

50

Seconds

60

Seconds

If the time delay selected is greater than 30 seconds, this time will apply only to the two detection circuits. The

manual release time delay will be clamped at 30 seconds.

Alarms

Selecting this button opens the “Alarms to Monitor...” dialog box. This scrolling list displays the alarms and

events related to the device that can be configured to be monitored by S

3

.

IPM • DETECTION CIRCUIT DELAY SELECTION