EAGLE QUANTUM PREMIER DEVICES

12-83

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Abort Mode

The IPM abort input, Channel 1, is software configurable to use any one of three modes of operation. These three

modes operate as follows:

Mode 1

Upon activation, the delay timer will count down to and hold at 10 seconds; upon release, timer will continue to

count down to zero.

Note

only this mode complies with UL 864.

Mode 2

Upon activation the delay timer will reset to its initial value and on release will continue counting down to zero.

IRI Mode

Functions similar to “Mode 1” except the abort will only function if activated prior to a second alarm.

Zone Modes

The IPM has two “zone modes”; Single or Cross Zoned. The backup logic will execute differently depending on

the zone mode selected.

IPM • CONFIGURATION

IPM • CONFIGURATION