Eqp logic editor, Item 150 - inhibit control, Item 151 - request ac voltage – Det-Tronics S3 Graphics User Manual

Page 308: Device item number descriptions

Advertising
background image

13-83

EQP LOGIC EDITOR

Version 6.0

Item 150 - Inhibit Control

Setting this control item instructs the controller to inhibit the device or channel associated with this item. Clearing

the item will remove the inhibit.
Inhibit control and status resides in the controller, not the field devices. Only the primary alarm or input status

is affected. Inhibits do not trigger a fault condition. When a device or a channel is inhibited, the controller will

illuminate one of two LEDs. When inputs are inhibited the Inhibit led will be activated and when an output

channel is inhibited the Out Inhibit led will be activated. Inhibits can be controlled from S

3

, user logic or from the

faceplate.
To change the inhibit state from the faceplate, navigate to the “Control Inhibit” property for the device or channel

and press the enter button, inhibit control will toggle. Resetting the controller or field device will not change the

inhibit state. Inhibits will persist through a download as long as the same device type remains at the address.

Inhibits will be lost during a loss of power or after a watchdog reset.
There are no built in time-outs for inhibit. An “Actual State” variable was added to show the state of an inhibited

input but S

3

does not currently display it. The “Actual State” variable is used by the controller when the inhibit is

removed. This allows the alarm or active condition to reactivate before the next status message from the device

arrives.
For SIL rated devices the master inhibit control must be enabled to allow inhibits to activate. See static logic

function for controller digital input #4 for more information.

Device

What is Inhibited

DCU

Low and High Gas Alarm

IDC

Input Active

UV_Detector

Fire Alarm

SAM

Output

ARM

Output

UV/IR

Fire Alarm

PSM

DCIO

Input Active or Output

Relay Module

Output

Eclipse

Low and High Gas Alarm

X3301/2/Automotive

Fire Alarm

X2200

Fire Alarm

X9800

Fire Alarm

X5200

Fire Alarm

Controller Relay

Output will not activate

Controller Digital Input

Input Active

AIM

Low and High Alarm

EDIO

Channel Active, Input or Output

EDIO_SIL

Channel Active, Input or Output

X3301_SIL

Fire Alarm

ECLIPSE_SIL

Low and High Gas Alarm

Item 151 - Request AC Voltage

Setting this control item instructs the controller to retrieve the AC voltage from the field device.

DEVICE ITEM NUMBER DESCRIPTIONS