EAGLE QUANTUM PREMIER CONFIG.

Version 6.0

EAGLE QUANTUM PREMIER CONFIG.

Reset Module

This command forces a selected field device to perform a “soft restart” effectively “rebooting” the field device.

This will also reset any latched alarms, faults, outputs, etc.

The reset command can be sent to a single selected device

or a group of devices. In the example to the right a group of

nodes 1-125 was selected from the LON schematic and the reset

command issued.

The controller then sent the reset command to the appropriate

devices and logged the activity to the “Reset Module(s)” dialog

box to provide feedback to the user.

Download

Sends all configuration data from S

3

’s LON configuration database

to the controller. This command must be used after changing the

configuration of a node, group of nodes, or controller logic.

To send configuration data to the devices on the LON, choose “Download”. This will cause S

3

to sequentially

download the configuration of all nodes, starting with LON address 1 and ending with the last configured node.

Get RTC

Requests the “Real Time Clock” data from the controller.

The gateway will return the current date and time, according

to its internal clock. Verify this date and time against that

of the S

3

station for accuracy. If it is not the same as the S

3

station, use the Set RTC command described later to correct

the discrepancy.