Alarm trigger direction, Alarms, Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 206

Advertising
background image

EAGLE QUANTUM PREMIER DEVICES

12-91

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Alarm Trigger Direction

In addition, each alarm has a checkbox to choose a “Falling Trigger”

alarm type.

When selected, the alarm will activate when the analog value drops

below the setpoint as its value is falling.

In the default configuration, a rising value activates the alarm as it passes

through the setpoint.

Gas Mode

Each channel can be configured to be used with a “Gas Detector” or

“Other (Non Gas)” instrument.

When a channel is configured as “Other” it can be used to monitor virtually

any linear analog value from a wide range of temperature, pressure, level

and other transmitter types.

When configured as a gas detector, regulatory requirements will preset

alarm setpoint ranges and certain alarm characteristics.

Common Settings

The bottom of the “AIM Editor...” dialog box contains buttons for setting all of the common settings on the

device.

Alarms

Selecting this button opens the “Alarms to Monitor...” dialog box.

This scrolling list displays the alarms and events related to the device that can be configured to be monitored

by S

3

.

AIM • GAS MODE