EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

DCIO/EDIO • STATIC LOGIC

Tagname

The tagname at the top of the dialog box refers to the entire module. Each of the eight channels also require a

tagname and until one is entered, that channel is not available in the S

3

database for programming, monitoring

or dynamic graphic purposes.

Type

Using a pull down menu each channel can be configured to be either an input or an output. When configured

as an input the channels will work with “dry” contact closure type devices. When configured as an output the

channels will power a 24 Vdc load.

Supervision

Via a pull down menu, the inputs and outputs may be software configured to supervise their attached device.

Available supervision options include “None”, “Open Circuit” detection, “Open and Short” circuit detection.

Activation Time

If a channel is configured as an output, an “Activation Time” (in seconds) can be entered. This feature works in

conjunction with the user program to simplify the logic and protect the field device. When being programmed in

the controller, if this channel is selected as a “Timed” output then the value entered in the “Activation Time” field

determines how long the output remains energized, even if the user logic keeps the output energized.