Standard Signal Processing

Standard signal processing is recommended for high speed suppression systems only. To allow for high speed

operation, the standard processing mode does not incorporate the arc rejection programming.

This mode should only be used in a controlled, indoor environment.

UV and IR Sensor Sensitivity Settings

Both the UV and IR detectors can be individually programmed to operate in one of four sensitivity settings; Low,

Medium, High or Very High.

The sensitivity level determines the maximum response distance and the response for the UVIR flame detector

as a whole will be the lesser of the two.

Examples of sensitivity settings are shown in the table below:

Combined Settings

The bottom portion of the dialog box contains settings for the alarm latching, Optical Integrity (Oi), input time

delay and PV deadband adjustments that apply to the whole detector as opposed to a specific sensor.

Alarm Latching Mode

The red LED on the face of the

detector comes on when in alarm

and can be configured to be either

latching or non-latching. If latching

is selected, following a fire detection,

the LED will stay on until the detector

is reset from the point display for

the detector in the S

3

software.

The default is non-latching.

Sensitivity

Arc Rejection

30 Inch Methane

1 Sq. Ft. Gasoline

1 Sq. Ft. Methanol

UV

Standard

Low

40

30

15

Medium

60

45

20

High

80

65

35

Very High

100

100

55

UV Arc

Rejection

Low

Medium

35

30

10

Low

High

35

30

10

Medium

Medium

55

40

15

Medium

High

55

40

15

High

Medium

60

50

25

High

High

65

50

25

Very High

Medium

85

65

50

Very High

High

85

65

50

IR

Low

40

65

40

Medium

55

75

45

High

65

90

55

Very High

90

100

60