Eqp logic editor – Det-Tronics S3 Graphics User Manual

Page 237

Advertising
background image

13-12

EQP LOGIC EDITOR

Version 6.0

EQP LOGIC EDITOR

In the example below the AB address “B20/0” is configured to be moved to a Premier controller global variable

“MCOP-FA001” and AB address “B20/1” in the process of being “dropped” onto a Premier controller global

memory point “MCOP-FA002”.

The radio buttons on the left hand side of the dialog box will determine

which configured global variables are displayed.

In the example to the right the “Boolean” radio button is selected and the

three configured boolean globals are displayed as potential targets for

data input.

Note

Data coming from an AB system into the Premier controller can only be

moved into global memory locations that have been configured using the

Global Memory editor as described on preceding pages of this manual.

When the “All to AB” tab is selected, a hierarchical list of “sources” is

shown on the left hand side of the dialog box which can be selected for

“movement” to “destinations” in the AB system.

Any item on the list that has a “+” before it

has subordinate items and clicking on the

“+” will expand the list showing all items that

make up that category. Below the list are two

buttons that can “Expand” or “Collapse” all

subordinate items in the list for easy viewing.

The first twelve items on the list provide

access to controller status information and

the globals database. The “LON” item will

allow access to all field device information,

the “Relays” item is for accessing the

controllers onboard relay status.

LOGIC EDITOR • CONTROLLER MENU