13-95

EQP LOGIC EDITOR

Version 6.0

Item 309 - One Zone Bell Tone

This item is used to select the bell tone when one zone of the IPM is in alarm and embedded logic mode is

enabled.

Value

Tone

0

Off

1

Continuous

2

60 BPM

3

120 BPM

4

Temporal

5

Trouble

6

Supervisory

Item 310 - Two Zone Bell Tone

This item is used to select the bell tone when the second zone of the IPM is in alarm and embedded logic mode

is enabled. See Item 309 for a list of available tones. The Marketing specification states that “The software will

prevent both selections (309 and 310) from being the same”.

Item 311 - Manual Release Delayed

First used with the IPM to select if the manual release input should be delayed or not. When set, the release

output will be delayed by the selected time, if cleared the release is immediate.

Item 312 - Serial Port 2 Protocol

The second configurable serial port protocol is set with this variable.

Serial Port Protocols

Value

Description

1

Port not used

2

Modbus Slave

3

Modbus Master

Item 313 - Serial Port 2 Baud Rate

The baud rate for the second configurable serial port is set with this variable. The default baud rate is 9600.

Baud Rate Codes

Code

Speed

3

9600

4

19.5K

5

38.4K

6

57.6K

7

115.2K

8

230.4K