EAGLE QUANTUM PREMIER DEVICES

12-29

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

Alarm Latching

This refers to the fire alarm “message” being sent from the detector to the EQP controller

and then used in both the embedded and user programmed logic. Non-latching is the

default and most common setting.

Using the Radio Buttons select either latching or non-latching for the alarm operation. If

set to latching, the user will have to reset the detector from its S

3

Point Display following

an alarm.

Time Delay

An input time delay can be programmed by entering a value from 1 to 15 seconds in

the provided field.

This will delay sending the fire alarm message to the EQP controller until the fire alarm

has been generated uninterrupted for the specified time. This programmable delay can

be used to filter out spurious events.

PV Deadband

A field is provided to enter the desired PV (Process Variable) Deadband.

Normally all values are transmitted to the controller every five seconds; If the PV changes more

than the entered percentage before the five second report time arrives, an immediate message is

sent with the current values.

Heater

A checkbox is provided to enable the Microprocessor controlled heated optics for increased

resistance to moisture and ice. In climates where this is not an issue, deselecting this option

will save up to 8 watts per detector.

X9800 • ALARM LATCHING