13-71

EQP LOGIC EDITOR

Version 6.0

Item 30 - Gas Mode

Gas Mode is used to determine if static logic should activate high and low gas alarms. When mode 1 is selected

static logic will activate the controller gas alarms. Mode 2 should be used for non-gas detector inputs.

Gas Mode

Value

Definition

1

Gas Detector

2

Other (Non Gas)

Item 31 - Engineering Zero Value

Zero range corresponds to the 4 ma value on the sensor input. For example, if 4 ma equates to 10.0 MPH of air

flow the engineering zero value should be set to 10.0.

Item 32 - Engineering Full Scale Value

Full scale range corresponds to the 20 ma value on the sensor input. For example, if 20 ma equates to 900.0

MPH of air flow the engineering zero value should be set to 900.0.

Item 33 - Calibration Level

This variable determines the calibration point for the 4 to 20 ma input. Valid values are in the range of 20 to 100%

of full scale.

Item 34 - Low Alarm Setpoint

Alarm setpoints must be within the limits listed on the DCU type code table. Alarm determination is done at the

DCU not the controller. However, user logic could be created within the controller to allow for many more alarm

levels.

Item 35 - High Alarm Setpoint

Alarm setpoints must be within the limits listed on the DCU type code table. Alarm determination is done at the

DCU not the controller. However, user logic could be created within the controller to allow for many more alarm

levels.

Item 36 - Units Text

This field holds the engineering units as a text string. The text string shall be displayed with the process variable

on the faceplate display. Future versions of DCUs with on board displays may also utilize this information for

display.

Item 37 - PV Change Dead-band

The process variable dead-band can be adjusted with this variable. This is only used during “Online” operation

and is expressed as a percentage of full scale. When the host computer instructs the controller to operate in online

mode the controller sends exception messages to the host computer when device variables change. However,

many analog values are constantly changing which many cause an abundance of unneeded messages. The “PV

Change Dead-band” variable is provided to limit how often the value is sent. The value must change by the “PV

Change Dead-band” amount or more fro the value to be sent.

DEVICE ITEM NUMBER DESCRIPTIONS

DEVICE ITEM NUMBER DESCRIPTIONS