Eqp logic editor, Item 39 - uv sensitivity, Item 40 - time delay – Det-Tronics S3 Graphics User Manual

Page 297: Item 41 - uv arc rejection, Item 42 - uv processing mode

Advertising
background image

13-72

EQP LOGIC EDITOR

Version 6.0

DEVICE ITEM NUMBER DESCRIPTIONS

Item 38 - Input Static Logic Mode

Input mode is used to determine if static logic should activate controller alarms on input activation. For example,

if mode 1 is selected, static logic will activate the controller fire alarm when the input is activated.

Mode

Definition

0

Invalid

1

Fire Alarm

2

Trouble

3

Low Gas Alarm

4

High Gas Alarm

5

Supervisory

6

Other

Item 39 - UV Sensitivity

Sensitivity

Value

Definition

Standard Mode

Star Mode

1

Low

96 cps

96 cups

2

Medium (Default)

48 cps

48 cps

3

High

24 cps

24 cps

4

Very High

8 cps

8/16 cps

Item 40 - Time Delay

Valid times are from 0 to 7 seconds with a default value of 5 seconds. This item is typically used to adjust the

amount of time a fire must persist before it is deemed to be an actual fire.

Item 41 - UV Arc Rejection

UV Arc Rejection

Value

Definition

Gate Length

1

Low

0.250

2

Medium (Default)

0.125

3

High

0.0625

4

Very High

0.0625

Item 42 - UV Processing Mode

UV processing mode can be selected with this variable.

UV Processing Mode

Value

Definition

0

Standard

1

STAR