13-14

EQP LOGIC EDITOR

Version 6.0

EQP LOGIC EDITOR

AB Table Settings

This menu selection opens a dialog box which allows up to

eight communication interface “tables” to be configured

to allow for data to be “moved” between the Eagle

Quantum Premier controller and an Allen-Bradley PLC

or other system utilizing Allen Bradley communication

protocols. Clicking on any cell in the “File Type” column

will activate a pop-up menu allowing the selection of the

proper table type for the data to be exchanged.

The three file types are binary, floating point (Float) and

Integer. To configure a table, select the appropriate file

type, file number, starting address and the number of

words to read (count). Once the tables are configured,

click the “OK” button to allocate memory to support the

new table configuration.

In the example above, table 1 is configured for binary data which will be stored in file 20. The table will be 128

words (16 bit registers) long and therefore support 2048 discrete “bits” of information.

MODBUS Export/Import

This selection allows the MODBUS settings created to be exported or imported to and from MS Excel or a text

editing program.

MODBUS Monitor

This dialog box is a tool for checking the value of data in any of the three configurable data tables used for

exchanging data between the Premier controller and Modbus RTU systems.

The desired table is selected with a radio button in the

top portion of the dialog box and a scrolling list displays

the data.

In the example to the right, the viewer has just been

activated and is attempting to establish communication

with the Premier controller.

LOGIC EDITOR • CONTROLLER MENU