Eqp logic editor, Item 291 - redundancy fault code, Item 292 - request manual switch – Det-Tronics S3 Graphics User Manual

Page 317: Item 293 - beeper status, Item 294 - communication option board type

Advertising
background image

13-92

EQP LOGIC EDITOR

Version 6.0

Item 291 - Redundancy Fault Code

This item can be used to determine the cause of a Redundancy fault.

Code

Description

0

No Fault

1

Alarm below threshold

2

No Comm From other controller

3

Parse Error

4

Ack Comm Error

5

Standby Fault

6

Program Flow Error

7

LON A Interface Fault

8

LON B Interface Fault

10

Application Memory Error

11

User Logic Error

12

Invalid Configuration

13

No Lon communication between controllers

14

Error in Response

Item 292 - Request Manual Switch

This control item is only used with a redundant controller configuration. When this bit is set in a Master controller

a switch to the standby controller is initiated. The switch will only occur if the standby controller is online and in

a health state.

Item 293 - Beeper Status

The status of the internal audible beeper is reflected with this variable.

Beeper Status

Value

Description

0

Off

1

Beeper Test (Active during lamp

test)

2

Gas Alarm

3

Trouble

4

Supervisory

5

Fire

Item 294 - Communication Option Board Type

This configuration item determines what type of Communication Option Board is attached.

Communication Board Type

Value

Description

0

None

1

Type A

DEVICE ITEM NUMBER DESCRIPTIONS

Advertising
This manual is related to the following products: