EQP LOGIC EDITOR

Version 6.0

Item 298 - Control Mode

This item selects the embedded logic control mode.

Value

Mode

0

Invalid

1

Embedded Logic Only

2

Controller Only

3

Back-up Mode

Embedded Logic Only:

In this mode the device will always use the embedded logic and ignore control messages

from the controller.
Controller Only:

In this mode the device will accept control information from the controller and never use

embedded logic. If communication with the controller is lost the outputs shall retain their last state.
Back-up Mode:

In this mode the device will accept control information from the controller and only use embedded

logic when communication with the controller is lost.

Item 299 - Detection Circuit Delay

This item allows the selection of a delay time that will apply to detector circuits, as well as a manual release (30

second max. for manual release, this will be handled by the field device). Time delay selection range from 0 to

60 seconds in 10-second increments. This could also be called an abort timer; it gives the user an opportunity

to hold off a release during an investigation time.

Item 300 - Abort Active

This item is true while the release abort input is active. First used with the IPM (DCIO smoke) module.

Item 301 - Manual Release Active

This item is true while the Manual Release input is active. First used with the IPM (DCIO smoke) module.

Item 302 and 303 - Zone 1 and 2 Alarm

These items reflect the alarm status of smoke detector loops. First used with the IPM (DCIO smoke) module.

Item 304 - Signal Circuit Active

This item is true while the alarm signal circuit (SAM output) is active. First used with the IPM (DCIO smoke)

module.

Item 305 and 306 - Release Circuit 1 and 2 Active

These items reflect the state of the release outputs. First used with the IPM (DCIO smoke) module.

Item 307 - Manual Reset Required

This item comes true when the IPM requires a manual reset.

Item 308 - Embedded Abort Timer

This item holds the amount of time remaining in the embedded abort timer.