Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 125

Advertising
background image

12-10

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

The definitions of the eleven columns in the “Alarms to Monitor...” dialog box are as follows:
Enabled
Turns an event on or off. If disabled, no other settings do anything.

Name
This 48 character field is used to describe the event or alarm. This is the text that will be used and recorded

throughout the S

3

applications suite when the event occurs.

Printer
When selected, sends the event to the S

3

event printer.

File
When selected, sends the event to the “Alarm History” module of S

3

for storage in the daily log.

Window
When selected, sends the event to the “Active Alarms” module of S

3

. This module is accessed via the F6 key

when online. It will also be displayed in the single line FIFO display at the bottom of the screen when in the

Online mode. Refer to Section 4.

Auto Clear

This selection determines whether the logged event will track the real time occurrence of the event or when the

operator acknowledgement is factored in.

If the AC checkbox is not selected, which is the default, when an event occurs it will be logged to the appropriate

locations, as configured by the Printer, File, Window selections, with the date and time of occurrence. When the

event returns to its normal state, nothing will happen until the operator activates the “Acknowledge” button. The

system will then log the date and time of the event returning to “Normal”. In reality it’s logging the first time the

operator activates the Acknowledge button after the event has returned to normal.

If the AC checkbox is selected, when an event occurs it will be logged to the appropriate locations, as configured

by the Printer, File, Window selections, with the date and time of occurrence. When the event returns to its normal

state, the system will then log the date and time of the event returning to “Normal”.

Sound
Each event may have a sound attached to it which plays when the event occurs, until the Acknowledge button

is actuated.

The sound can be the default “Warning” or any of sixty three custom sounds. Use the pull down menu to select

the desired sound.

EQP CONTROLLER • ALARMS & EVENTS

Advertising
This manual is related to the following products: